Overheating guide

Overheating guide

Last updated: 17/11/2026

Vulcan checks a dwelling for overheating risk from the same model you use for HEM. It uses EnergyPlus 26.1 in the browser, one zone per room. It does not change the HEM calculation.

Overheating is a preview for selected Pro accounts. For the validation evidence, see Overheating: validation and conformance.

Methods

Method What it does Available
Part O · simplified method Approved Document O Section 1. Checks glazing area and free area against Tables 1.1–1.4 for a high or moderate risk location. No simulation Yes, England
Part O · dynamic (TM59) Approved Document O dynamic thermal modelling with CIBSE TM59:2017. Window, door and night rules of AD O §2.6 Yes, England
TM59 (2017) CIBSE TM59:2017 design method. Windows open when the room is occupied and above 22 °C Yes
TM59 (2026) CIBSE TM59:2026, Stages 1 to 3. Windows open on the room's operative temperature, on UK clock time Yes

Part O dynamic and TM59 (2017) use the TM59:2017 profiles and criteria:

  • Criterion A (living rooms, kitchens, bedrooms): hours from May to September at least 1 K above the adaptive comfort limit must not exceed 3 % of occupied hours.
  • Criterion B (bedrooms): operative temperature above 26 °C from 22:00 to 07:00 must not exceed 1 % of annual hours (32 h).
  • A room whose openable area is below 1/20 of its floor area takes the fixed test instead: above 26 °C for no more than 3 % of its occupied hours (TM59:2017 §4.3). The run notes say so.

TM59 (2026) uses the TM59:2026 profiles and criteria, on UK clock time:

  • Criterion a (living rooms, kitchens, bedrooms): as A, from May to September, 3 % of occupied hours.
  • Criterion b (bedrooms): the mean operative temperature of the night (23:00–08:00) is above 27 °C (26 °C for Category I) on no more than 4 nights from May to September.
  • Stage 1 is the passive design. Stage 2 adds each window's site restriction, if any. Stage 3 adds cooling, only when Stage 2 fails and the model has a cooling system. The verdict is the last stage's. A run made before TM59 (2026) was available has no verdict; run it again.

Run a check

  1. Open the model. In Quick sim settings, turn on overheating for the model's project. Choose the method and the weather file. For TM59, choose the comfort category (default II).
  2. Fix the issues the editor shows. Each issue names the element and the fix.
  3. Run. Quick sim shows "Passes · N to confirm" or "Fails · N rooms", with the list of items the assessor confirms. For TM59 (2026), Results shows each stage; an earlier stage's row says which stage fails.
  4. Open Results. Summary gives each room's criteria as hours exceeded against hours allowed. Temperature, Season and Ventilation show the hourly values.
  5. Export the evidence report, the room metrics CSV and the run files.

The evidence report prints the run date and "Modeller:" with the name of the signed-in account that made the run. A run made with no signed-in account prints "Modeller: not stated". The report has no reviewer field.

Inputs

Vulcan reads geometry, constructions, openings, ventilation and the site from the HEM model. Overheating adds the inputs below. Each has a default; you change it only when the design differs.

Windows and doors

Input Default and convention
Opens as Window, patio door or entrance door. Default from the drawing: glazing that starts at the floor is a patio door. An entrance door stays shut
How it opens, Opens to The opening style and angle. They set the equivalent area from AD O Appendix D, Tables D1–D9
Equivalent area Default: the Appendix D value, shown as the placeholder. A value you enter replaces it
Security risk The HEM window field. Vulcan finds whether a window is easily accessible from the geometry (AD O Appendix A): within 2 m of the ground, or within 2 m vertically of a roof pitched under 30° whose lowest point is within 3.5 m of the ground. An accessible window opens at night only if you enter Security risk No
Guarding fitted Default not ticked. An opening that needs guarding (AD O §3.9, Table 3.1) stays shut until you tick it. The assessor confirms the guarding
Storey From HEM Storey of dwelling. When it is not set, a room whose floor is 2 m or more above the ground counts as first floor or above

A window in a hall, landing, bathroom, WC or utility room opens only if it is not easily accessible, or if you enter Security risk No.

Rooms (Space Labeller)

Input Default and convention
Windows closed at night for noise Bedrooms. Default not ticked. Tick when night noise is above 40 dB LAeq over 8 hours or 55 dB LAFmax more than 10 times (AD O §3.3). The windows stay shut 23:00–07:00
Double bed fits Bedrooms. Default from the room size (11.5 m² and 2.55 m wide). TM59 uses two occupants when a double bed fits
Ceiling fan Default none
Chimney breast Default none. Width and depth; modelled as internal brickwork mass
Pipework heat gain Communal rooms (corridor, stair, lobby). No default: enter the design value in watts, or 0

Homes with more than 3 bedrooms get occupant gains pro rata (TM59:2017 §5.3 note 1). The run notes say so.

Ventilation and cooling

Input Default and convention
HEM vents Modelled on every route, always open, at their equivalent area
MVHR: Has a summer bypass Default not ticked: heat recovery all year, as in HEM. Ticked: bypass, no heat recovery, from May to September
MEV boost TM59:2026 only, Stage 2. Not used on the 2017 routes
Cooling TM59:2026 Stage 3 only, from the HEM cooling system and its capacity. Not modelled on the 2017 routes

Weather

Use a suitable licensed CIBSE file through the weather selection. For Part O and TM59 (2017), use the 2016-generation DSY1, 2020s, high emissions, 50th percentile file for the location. For TM59 (2026), use the 2025-generation DSY1, 2050s, RCP8.5, 50th percentile file, release 1.1. Vulcan reads the file identity from the header. A DSY2 or DSY3 run is a sensitivity run on every TM59 method; the pass basis is DSY1.

Assumptions

  • Each room is one well-mixed air zone. There is no temperature gradient within a room.
  • The ground is a static temperature from the HEM slab method and the monthly means of the weather file.
  • The fabric is HEM's: each construction becomes equivalent layers with the same thermal resistance, areal heat capacity and mass position.
  • Glazing uses the whole-window U-value and g × (1 − frame fraction), as HEM defines g.
  • Wind exposure comes from the HEM terrain class (default Suburban). Wind pressure uses low-rise surface-average coefficients. Only the dwelling is modelled, not the whole building, and no site shielding.
  • Space heating is not modelled.
  • Results are idealised. A change to the model marks a saved run "changed".

Limits

  • Wales and Scotland: guarding uses the Approved Document O (England) thresholds. The Welsh and Scottish guidance is not applied.
  • Cooling is not modelled on the TM59:2017 and Part O routes.
  • MVHR boost is not modelled.
  • On HEM:FHS a9, walls, roofs, floors and doors take areal heat capacity as a class, and the lightest class is 240 kJ/m²K (Very light). A lighter element is modelled with more thermal mass than it has. Partitions, and every element on HEM:EPC, take the number entered.
  • Heat networks: pipework heat gain has no default. Enter the design value for each room it runs through.
  • Vulcan does not model the airflow resistance of curtains or blinds over open windows.

Tutorial: the worked example

The worked example is a two-storey test house. It is a test model, not a real dwelling.

Item Value
Form Two stacked 8 m × 8 m floors, 128 m², 2.8 m storey height, flat roof. Vulcan assumes a stairwell between the halls
Rooms per floor Living (25.4 m²), Bedroom (24 m²), Hall (14.6 m²). The halls are not assessed
Walls, floors, roof R 3 m²K/W, Medium areal heat capacity, mass at the inside face
Windows Four, 1.0 m × 1.2 m, sill 0.8 m above the floor. Living rooms face north, bedrooms face south. U 1.2 W/m²K, g 0.6, frame fraction 0.25. Overhang 0.6 m deep, 0.1 m above each window. Guarding fitted not ticked
Opening Maximum openable area 0.5 m²; equivalent area 0.32 m²
Airtightness 3 m³/(h·m²) at 50 Pa
Site Postcode MK42 0AA (England); terrain open field

Steps:

  1. Draw the model from the table on HEM:FHS 1.0.0a9. Leave the defaults empty.
  2. In Quick sim settings, choose the method and the weather file RAF_Bedford_01.epw (an engineering weather file, not CIBSE data, declared as DSY1 for this test). Run.
  3. Read the verdict in Quick sim, then each room in Results. Read the run notes.
  4. Compare your hours with the expected answers below.

Expected answers (recorded 17 November 2026; hours or nights exceeded / allowed):

Room TM59 (2017) Part O · dynamic (TM59) TM59 (2026) a TM59 (2026) b
Bedroom 0 / 262 h 4 / 262 h 0 / 110 h 0 / 4 nights
First floor Bedroom 0 / 262 h 233 / 262 h 0 / 110 h 11 / 4 nights
Living 0 / 142 h 0 / 142 h 0 / 59 h Not applicable
First floor Living 0 / 142 h 82 / 142 h 0 / 59 h Not applicable
Quick sim Passes · 2 to confirm Passes · 3 to confirm Fails · 1 room

On the 2017 methods each room's openable area is below 1/20 of its floor area, so every room takes the fixed 26 °C test. On Part O and TM59 (2026) the first-floor windows stay shut, because they need guarding and Guarding fitted is not ticked. TM59 (2026) fails at Stage 1: the first-floor bedroom is too warm on 11 nights.