Overheating: assumptions and limits

Overheating: assumptions and limits

Last updated: 29/11/2026

Where Vulcan makes a choice that CIBSE TM59 or Approved Document O does not make, and what Vulcan cannot model yet. Each line gives the source it reads.

Assumptions

Which criteria apply

  • The 1/20 opening test (TM59:2017). Each habitable room must open at least 1/20 of its floor area, or the whole home takes the fixed 26 °C test (TM59:2017 §4.1, §4.3). Part F measures the height × width of the part that opens. Vulcan counts the maximum open area of each window as you enter it.
  • Windows that open less than half the time (TM59:2026). At Stage 2, a room whose windows can open for less than half its occupied hours takes Criterion c, and a bedroom or studio also takes b, with or without mechanical ventilation (TM59:2026 §2.3).
  • Studios. A studio also takes the bedroom night criterion (TM59:2017 Criterion B, TM59:2026 Criterion b), because people sleep in it. The method gives that criterion to bedrooms only (TM59:2017 §4.2, TM59:2026 §2.4.2).
  • The comfort limit (TM59:2017). The limit follows the TM52 line at every running mean outdoor temperature (TM52 §6.1.2). TM59:2026 holds it fixed below 10 °C and above 30 °C (TM59:2026 §2.4.1).

Windows and doors

  • Window restrictors. A window that a fixed restrictor holds to 100 mm or less needs no guarding, and opens at its area with the restrictor in place (Approved Document O FAQ 20; Approved Document O §3.9). Confirm that the restrictor is fixed. A sash longer than about 0.57 m then opens less than 10°, below the Approved Document O Appendix D tables, so enter its equivalent area.
  • Upper-floor patio doors (Part O dynamic). Vulcan cannot draw a balcony, so it treats a patio door above the ground floor as an upper-floor window. In a bedroom, it opens at night when the room is above 23 °C at 23:00. It opens only with guarding 1.1 m high (Approved Document O §2.6, Table 3.1). If it opens onto a balcony, set Security risk to Yes.
  • How far a window opens (Part O dynamic). A window starts to open at 22 °C room air temperature and is fully open at 26 °C, in a straight line between the two (Approved Document O §2.6).
  • Ground-floor bedrooms at night (Part O dynamic). Approved Document O gives the 23:00 rule for upper-floor windows (Approved Document O §2.6). Vulcan also applies it to the secure part of a ground-floor or easily accessible bedroom window: that part opens if the room is above 23 °C at 23:00, until 08:00 (Approved Document O §3.6).
  • Corridor windows. On TM59:2017 design, a corridor window opens above 22 °C at any hour, as designed (TM59:2017 §3.9). On Part O dynamic, windows open by day only in occupied rooms, and a corridor has no occupancy (TM59:2017 Table 2), so an upper-floor corridor window opens only at night (Approved Document O §2.6).

Times

  • Clock for Part O times. Approved Document O does not say which clock its times use. Vulcan uses GMT, as TM59:2017 does (TM59:2017 Table 2). In summer, 23:00 GMT is midnight on the clock. TM59:2026 runs use UK clock time.
  • Stage 3 cooling hours. A cooling system with its own HEM control cools at the set point and hours of that control, on GMT as HEM runs them, so they are an hour later on the clock in summer. A cooled bedroom gets a warning when that control does not cool all night.
  • Stage 3 cooling with no control. A cooling system with no control of its own cools the room to 24 °C, HEM's default cooling set point, at all hours. The windows open first, so the cooling runs only when they cannot keep the room at 24 °C. The method runs cooling only when natural ventilation cannot keep the room at its set point (TM59:2026 §3.5). HEM's default cooling hours are not used, because they do not cool a bedroom through the night.

Rooms

  • Home offices and studies (TM59:2017). TM59:2017 lists bedrooms, living rooms and kitchens only. A home office, dining room or study gets lighting gains only, no criteria, and is not in the 1/20 test. TM59:2026 gives a home office its own criteria (TM59:2026 §2.4).
  • Open en-suites and utility rooms. A room with no wall between two labels is one room. When one label is a bedroom, living room, kitchen or studio (on TM59 (2026) also a home office) and the other is a bathroom (an en-suite), WC, utility, hall, void or a room TM59 does not list, the room takes the gains and criteria of the first label (TM59:2026 §3.7.1; TM59:2017 Table 2 notes 1 and 3). Draw the wall between them to assess two rooms.
  • Combined rooms (TM59 (2026)). A room with no wall between two labels that TM59 gives gains to takes one space type. A bedroom, living room and kitchen together is a studio. Any other room with a bedroom is a bedroom. A living room or a kitchen with a home office is that living room or kitchen. This is Vulcan's convention: TM59 says home working is part of the living room's gains, and names no kitchen (TM59:2026 §3.7.1). Over a day, the kitchen's gains are lower than a home office's; they are higher from 18:00 to 20:00 and at night. Draw the wall between them to assess two rooms.

Heat flow in the model

  • Window U-values. Vulcan uses each window's U-value as you enter it. It does not add the curtain resistance that HEM adds for its energy run.
  • Colour of outside surfaces. An outside wall or roof with no colour given absorbs 60% of the sun on it.
  • Heat from people and appliances. 30% of the heat from people is radiant. Heat from equipment and lighting is all convective. TM59 lets the modeller choose this split.
  • Overhangs, side fins and nearby obstacles. HEM takes each one as endless. Vulcan extends each one across its wall to the next window or the end of the wall, and two windows with the same kind meet halfway. A nearby obstacle is a wall at its distance from the window, from the ground to its height, that lets through its transparency.
  • Flat roof windows. Air goes through a roof window within 10° of level one way at a time, as EnergyPlus models it. A sloped roof window opens as a wall window does.
  • MVHR heat recovery. An MVHR with no heat recovery efficiency entered recovers no heat, as in HEM.
  • No air test (HEM:EPC). An existing home with no air test takes the air leakage that the EPC calculation estimates. The run notes and the Report say "estimated". Enter the air test result when the home has one.
  • Stairs. Each stair is one opening that is always open, up to a landing labelled Hall. It rises from the hall under the landing. When no hall is under a landing on that storey, it rises from the largest room under the landing, for example a living room with an open stair.
  • Heat sources. A boiler, heat pump, heat source on a heat network, combi boiler, point-of-use water heater or combustion appliance adds no heat gain: space heating is off from May to September, and TM59 lists gains for cylinders, HIUs, pipework and heat tape only (TM59:2026 §3.7.2; TM59:2017 §3.8). TM59 (2026) cannot model a heat battery or a smart hot water tank yet.
  • Heat maintenance tape. In any home, the assessor enters the heat gain of heat tape, at 8 W per metre run, plus the heat loss of the pipework it keeps hot, as the Pipework heat gain of each room it runs through (TM59:2026 §3.7.2; TM59:2017 §3.8). With a heat tape control system, only the pipework's standing loss is entered. On TM59 (2026), for an existing home on HEM:EPC, the EPC calculation gives the hot water pipework, so the assessor enters only the heat tape (TM59:2026 §3.7.2). Vulcan takes a room with no value as a room with no heat tape.
  • MVHR boost. In TM59 (2026) Stages 2 and 3, an MVHR with a boost rate raises its supply and extract together to that rate when a room is occupied, its windows are kept shut by a site constraint, it is above 26 °C and the outdoor air is cooler than the room air. Warmer outdoor air would heat the room, so the boost stays off then. EnergyPlus cannot change a fixed air flow during a run, so Vulcan adds the extra air as a heat flow in each room the MVHR supplies, with the heat recovery and the summer bypass of the design flow. The extra fan heat is added too. The rooms the air passes through to the extract, such as a kitchen, keep the design flow. The method models higher flow rates only when they are necessary and gives no control, so Vulcan uses the same rule as for a central MEV (TM59:2026 §3.5).
  • Open flues and chimneys (HEM:EPC). Each flue or passive duct in a HEM:EPC model is an air path from its room to outdoors that is always open. Its resistance is HEM's: the air terminal, the duct and the cowl with no wind. HEM leaves out the cowl's loss when the wind blows, and Vulcan keeps it at all hours, so the flue flow is a little lower than HEM's in wind. Its top is at HEM's stack height above the ventilation zone base: the duct length plus 2 m, or the zone height plus 2 m when the zone is more than 3 m high. The room is the room of the heater that uses the flue, else of the duct's own row: the room its drawn point is in on its storey, else the largest room of its zone. The run notes say when Vulcan takes the largest room. EnergyPlus applies its roof wind pressure at the top, where HEM uses the cowl's tested factor. A hybrid duct's fan is not modelled. The air an appliance draws while it fires is not modelled. The space heating is off in the run, but an appliance that also heats water still fires.
  • Suspended floors. The ground under a suspended floor has a monthly temperature from HEM's correction of BS EN ISO 13370 (H.6.2 and H.6.3), which HEM:EPC uses. The HEM:FHS 1.0.0a9 and 1.0.0a7 engines use the equations as the standard prints them, which are in the wrong units. A suspended floor also uses the annual mean wind speed of the weather file.

Part O simplified method

  • Most glazed room. The most glazed room is the room with the largest glazing area in m². If two rooms have the same area, the room with more glazing for its floor area is used. An open-plan room counts only to 4.5 m from its glazed wall (Future Homes Hub Part O guidance, 2022; Approved Document O Appendix A).

Weather

  • Weather site (TM59:2017, Part O dynamic). Vulcan warns when a CIBSE weather file is not for the CIBSE location nearest the postcode, measured from the middle of the postcode district. The three London files all count as London. TM59 asks for the file most appropriate to the site, and the nearest file may not suit a local microclimate (TM59:2017 §3.2; Approved Document O §2.2), so check the choice yourself.

Limitations

Heat flow in the model limitations

  • Lofts. An unheated loft is not its own space. Its roof takes sun and sky as a flat roof at ceiling height, not at its pitch.
  • Open-flue appliances (HEM:FHS). HEM:FHS holds no flue size for a combustion appliance and leaves it out of its ventilation, so the air that flows through its flue is not modelled. The run gives a warning on the row.

Part O simplified method limitations

  • Shading in a high risk location. The model has no shutters and does not test the angle of an overhang. So the shading row cannot fail: the check passes only if you confirm that the windows have that shading (Approved Document O §1.9).

Weather limitations

  • Weather zone (TM59:2026). Vulcan cannot check that the weather file is for the zone of the site. Find the zone with the CIBSE Weather Data Selection Tool.